Standard Dimensions
Series 2500/2500-1 | ||||||
---|---|---|---|---|---|---|
Valve Size | 2-1/2" | 3" | 2" | 4" | 6" | 8" |
A | 11.03 | 11.84 | 8.44 | 13.91 | 17.12 | 20.47 |
B | 12 | N/A | 9.36 | N/A | N/A | N/A |
End to End | 11.12 | 11.38 | 10.75 | 13 | 15.88 | 17.5 |
NOTES
- 3" through 8" valves meet or exceed requirements of ANSI/AWWA C515.
- 2-1/2" through 8" valves may be ordered in configurations that are UL Listed and FM Approved.
- 2" through 8" valves have 250 psig AWWA rated working pressure.
- 2-1/2" through 8" valves have 250 psig UL and FM rated working pressure.
- Fusion-bonded epoxy coating meets or exceeds requirements of ASME/AWWA C550.
- PVC ends are suitable for use on steel (IPS) sizes of PVC or steel pipe.
- MAINTENANCE: Each valve should be operated through a full cycle and returned to its normal position. This should be done on a time schedule that is designed to prevent a buildup of tuberculation or other deposits that could render the valve inoperable or prevent a tight shutoff. It is recommended that this be done once a year.
- Open direction is specified by the customer.