5 1/4" American-Darling B-62-B-5

Depth of
Trench
Length of
Lower Rod
2’-0" 19.88"
2’-6" 25.88"
3’-0" 31.88"
3’-6" 37.88"
4’-0" 43.88"
4’-6" 49.88"
5’-0" 55.88"
5’-6" 61.88"
6’-0" 67.88"
6’-6" 73.88"
7’-0" 79.88"
7’-6" 85.88"
8’-0" 91.88"
8’-6" 97.88"
9’-0" 103.88"
9’-6" 109.88"
10’-0" 115.88"
10’-6" 121.88"
11’-0" 127.88"
11’-6" 133.88"
12’-0" 139.88"
12’-6" 145.88"
13’-0" 151.88"
13’-6" 157.88"
14’-0" 163.88"
14’-6" 169.88"
15’-0" 175.88"
15’-6" 181.88"
16’-0" 187.88"
16’-6" 193.88"
17’-0" 199.88"
17’-6" 205.88"
18’-0" 211.88"
18’-6" 217.88"
19’-0" 223.88"
19’-6" 229.88"
20’-0" 235.88"

NOTES

  1. Depth of trench is the nominal distance from groundline to bottom of connecting pipe.
  2. Size and shape of nut on operating nut and cap, threading on nozzles and caps, and the direction of opening made to specifications.
  3. Cap chains are furnished unless specified otherwise.
  4. Working pressure 200 psig; test pressure 400 psig.
  5. Hydrant conforms to AWWA specifications C502.
  6. Upper barrel can be rotated 360°.
  7. FM Approved and UL Listed at 200 psig in allowable configurations.

Request More Information